Tripp Lite SM2200RMXL2UTAA TAA SmartPro 120V 2.2kVA 1.92kW Line-Interactive Sine Wave UPS, 2U, Extended Run, Network Card Options, LCD, USB, DB9

TRIPPLITE-SM2200RMXL2UTAA
SM2200RMXL2UTAA
Tripp Lite

Regular Price: $1,598.40

  • Product Description
  • Reviews
  • Additional Information
  • Tags
  • Product Video
  • Specifications

The SM2200RMXL2UTAA is compliant with the Federal Trade Agreements Act (TAA) for GSA Schedule purchases. Tripp Lite SmartPro Line Interactive UPS with enhanced LCD interface offers network-grade power protection for critical server, network and telecommunications equipment. Line Interactive Uninterruptible Power Supply (UPS) with built-in Auto-Voltage Regulation (AVR) actively corrects brownouts and overvoltages back to usable levels while maintaining a full battery charge in case of power failure. Tripp Lite's unique configuration excels in exceptionally poor-power environments with two separate levels of voltage boost to correct both slight undervoltages and severe brownout conditions. Interactive LCD interface reports UPS operating mode, detailed UPS and site-power data, plus enables a variety of UPS setup and configuration options. Super-fast switchover from line to battery power occurs within milliseconds to maintain operation of connected equipment without interruption or reboot. 96% line-mode efficiency offers reduced heat emissions and operating costs. Communications interfaces support communications via USB, DB9 serial and a slot for an optional network management card. HID-compliant USB port enables integration with built-in power management and auto shutdown features of Windows and Mac OS X. Network communications ports enable detailed monitoring of equipment load levels, self-test data and utility power conditions. PowerAlert UPS monitoring and auto-shutdown software is available via free download. Switched output load banks enable scheduled and real-time remote reboot and load shedding of select outlets. Emergency Power Off (EPO) interface. LCD display panel easily rotates for viewing in rackmount or tower configurations. Audible alarm with push-button momentary alarm-cancel and silent-mode configuration options. Programmable self-test. Field-replaceable, hot-swappable battery modules.

Features

  • Compliant with the Federal Trade Agreements Act (TAA) for GSA Schedule purchases
  • Tripp Lite SMART2200RMXL2U line interactive 2U rack/tower UPS with 2200VA / 2.2kVA / 1920W capacity and extended runtime options Line interactive UPS with Automatic Voltage Regulation (AVR) corrects brownouts and overvoltages from 83 to 145V
  • NEMA 5-20P input plug; 4 NEMA 5-15/20R and 4 5-15R output receptacles, Two independently switched output load banks
  • Maintains uninterrupted operation of connected networking equipment during blackouts, surges, brownouts and overvoltages
  • High 96% efficiency rating in line-power mode offers reduced power consumption and BTU emissions
  • Internal batteries offer 12 minutes at 50% load (960W) and 4.5 minutes at 100% load (1920W)
  • Extended runtime is available with optional BP48V24-2U / BP48V242UTAA (limit 1) OR BP48V60RT3U / BP48V60RT3UTAA (no limit), Output is reduced to 1600 watts maximum with external battery packs
  • External battery configurations require the use of Tripp Lite's External Battery Configuration Software (see manual)
  • Hot-swappable, user-replaceable internal batteries and external battery packs can be replaced with no disruption to connected equipment
  • Following an extended power outage, the UPS will automatically restart into line-power mode, begin powering connected equipment and recharge the battery system, all without user interaction
  • Front panel LCD monitoring screen with MODE and ENTER buttons reports operating mode with 5-bar battery charge graphic, plus 7 selectable screens of detailed UPS and site power information
  • LCD interface also supports a number of advanced user setup and operating preferences
  • Ships with 4 post rackmount installation hardware; Optional 2POSTRMKITWM enables 2 post rackmount/wallmount installation; Optional 2-9USTAND enables tower placement
  • Communications interfaces support communications via USB, DB9 serial and slot for network management card options; Compatible with Tripp Lite UPS management card options TLNETCARD, WEBCARDLX and SNMPWEBCARD
  • HID-compliant USB port enables integration with built-in power management and auto shutdown features of Windows and Mac OS X
  • USB & Serial ports enable data-saving unattended shutdown when used with Tripp Lite's PowerAlert software, available via FREE download from www.tripplite.com/poweralert
  • Built-in Emergency Power Off (EPO) interface with cable
  • This product is ENERGY STAR qualified for its ability to save customers money while helping to protect the environment

Package Includes

  • SM2200RMXL2UTAA TAA Compliant UPS system
  • USB, Serial & EPO cabling
  • 4 post installation kit
  • Owner's manual
Product Condition New
Manufacturer part number SM2200RMXL2UTAA
Manufacturer Tripp Lite
Specifications
OVERVIEW
UPC Code 037332152800
OUTPUT
Output Volt Amp Capacity (VA) 2200
Output kVA Capacity (kVA) 2.20
Output Watt Capacity (Watts) 1920
Output kW Capacity (kW) 1.92
Output Capacity Details Output is reduced to 1600 watts maximum when used with external battery packs
Power Factor 0.87
Nominal Output Voltage(s) Supported 110V; 115V; 120V
Nominal Voltage Details 120v nominal output in battery mode
Frequency Compatibility 60 Hz
Output Voltage Regulation (Line Mode) -14%, +6%
Output Voltage Regulation (Battery Mode) +/- 5%
Output Receptacles (4) 5-15R; (4) 5-15/20R
Load Management Receptacles Two switched single outlet load banks (1 5-15/20R & 1 5-15R)
Output AC Waveform (AC Mode) Sine wave
Output AC Waveform (Battery Mode) Pure Sine wave
INPUT
Rated input current (Maximum Load) 16A (120V)
Nominal Input Voltage(s) Supported 120V AC
UPS Input Connection Type 5-20P
UPS Input Cord Length (ft.) 10
Recommended Electrical Service 20A 120V
Input Phase Single-Phase
BATTERY
Full Load Runtime (min.) 4.5 min. (1920w)
Half Load Runtime (min.) 12 min. (960w)
Expandable Battery Runtime Extended runtime supported via optional external battery packs; 1600 watts maximum load with external battery packs
External Battery Pack Compatibility  BP48V24-2U (limit 1);  BP48V242UTAA (limit 1);  BP48V27-2US (multi-pack compatible);  BP48V60RT-3U (multi-pack compatible);  BP48V60RT3UTAA (multi-pack compatible)
DC System Voltage (VDC) 48
Battery Recharge Rate (Included Batteries) Less than 4.5 hours from 10% to 90%
Internal UPS Replacement Battery Cartridge  RBC94-2U 
Battery Access Front panel battery access door
Battery Replacement Description Hot-swappable, user replaceable batteries
Expandable Runtime Yes
VOLTAGE REGULATION
Voltage Regulation Description Automatic voltage regulation (AVR) maintains line power operation with an input voltage range of 83 to 145
Overvoltage Correction Voltage reduction of 12% applies when input is between 127 and 145
Undervoltage Correction Voltage boost of 12% applies when input voltage is between 96 and 108
Severe Undervoltage Correction Voltage boost of 24% applies when input voltage is between 83 and 95
USER INTERFACE, ALERTS & CONTROLS
Front Panel LCD Display Front panel LCD information and configuration screen offers detailed UPS and site power status and operating data, plus configuration of voltage, operating mode, alarm function and a variety of additional options (see manual for detailed LCD configuration and monitoring options)
Switches Power-fail alarm can be temporarily silenced using alarm-cancel switch; silent mode alarm configuration option available
Alarm Cancel Operation Power-fail alarm can be temporarily silenced using alarm-cancel switch; silent mode alarm configuration option available
Audible Alarm Audible alarm indicates UPS startup, power-failure, low-battery, overload, UPS fault and remote shutdown conditions
SURGE / NOISE SUPPRESSION
UPS AC Suppression Joule Rating 570
UPS AC Suppression Response Time Instantaneous
EMI / RFI AC Noise Suppression Yes
PHYSICAL
Installation Form Factors Supported with Included Accessories 4 post 19 inch rackmount
Installation Form Factors Supported with Optional Accessories 2 post rackmount (2POSTRMKITWM); Wallmount (2POSTRMKITWM); Tower (2-9USTAND)
Primary Form Factor Rackmount
UPS Power Module Dimensions (hwd, in.) 3.46 x 17.32 x 19.29
Rack Height (U Spaces) 2
Minimum Required Rack Depth (inches) 24.5
UPS Power Module Weight (lbs.) 57.6
UPS Power Module Weight (kg) 26.13
Shipping Dimensions (hwd / in.) 8.800 x 24.000 x 20.900
Shipping Weight (lbs.) 72.7000
Cooling Method Fan
UPS Housing Material Steel
Primary UPS Height (mm) 879
Primary UPS Width (mm) 4,399
Primary UPS Depth (mm) 4,900
ENVIRONMENTAL
Operating Temperature Range +32 to +104 degrees Fahrenheit / 0 to +40 degrees Celsius
Storage Temperature Range +5 to +122 degrees Fahrenheit / -15 to +50 degrees Celsius
Relative Humidity 0 to 95%, non-condensing
AC Mode BTU / Hr. (Full Load) 306
Battery Mode BTU / Hr. (Full Load) 1157
COMMUNICATIONS
Communications Interface USB (HID enabled); DB9 Serial; EPO (emergency power off); Slot for SNMP/Web interface
Network Management Cards SNMPWEBCARD; TLNETCARD;  WEBCARDLX 
Network Monitoring Port Description Supports detailed monitoring of UPS and site power conditions
PowerAlert Software For local monitoring via the UPS’s built-in communication ports, download PowerAlert Local software at http://www.tripplite.com/poweralert
Communications Cable USB and DB9 cabling included
WatchDog Compatibility Supports Watchdog application, OS and hard-reboot restart options for remote applications
Network UPS Tools Compatibility NUT compatible. See the full list of Tripp Lite NUT compatible UPS systems at http://www.networkupstools.org/stable-hcl.html?manufacturer=Tripp Lite
LINE / BATTERY TRANSFER
Transfer Time 5 milliseconds (line to battery mode); 1 millisecond (battery to line mode)
Low Voltage Transfer to Battery Power (Setpoint) 83
High Voltage Transfer to Battery Power (Setpoint) 145
SPECIAL FEATURES
Grounding Lug Back panel grounding lug
Cold Start (Startup in Battery Mode During a Power Failure) Cold-start operation supported
High Availability UPS Features Hot swappable batteries
Green Energy-Saving Features Greater than 95% efficiency - GREEN UPS; Individually controllable load banks
CERTIFICATIONS
UPS Certifications ENERGY STAR Qualified; Meets FCC Part 15 Category A (EMI); ROHS (Restriction of Hazardous Substances); TAA Compliant; Tested to CSA (Canada); Tested to NOM (Mexico); Tested to UL1778 (USA)
WARRANTY
Product Warranty Period (Worldwide) 2-year limited warranty
Connected Equipment Insurance (U.S., Canada & Puerto Rico) $250,000 Ultimate Lifetime Insurance 
 

Product Tags

Use spaces to separate tags. Use single quotes (') for phrases.

 
OVERVIEW
UPC Code 037332152800
OUTPUT
Output Volt Amp Capacity (VA) 2200
Output kVA Capacity (kVA) 2.20
Output Watt Capacity (Watts) 1920
Output kW Capacity (kW) 1.92
Output Capacity Details Output is reduced to 1600 watts maximum when used with external battery packs
Power Factor 0.87
Nominal Output Voltage(s) Supported 110V; 115V; 120V
Nominal Voltage Details 120v nominal output in battery mode
Frequency Compatibility 60 Hz
Output Voltage Regulation (Line Mode) -14%, +6%
Output Voltage Regulation (Battery Mode) +/- 5%
Output Receptacles (4) 5-15R; (4) 5-15/20R
Load Management Receptacles Two switched single outlet load banks (1 5-15/20R & 1 5-15R)
Output AC Waveform (AC Mode) Sine wave
Output AC Waveform (Battery Mode) Pure Sine wave
INPUT
Rated input current (Maximum Load) 16A (120V)
Nominal Input Voltage(s) Supported 120V AC
UPS Input Connection Type 5-20P
UPS Input Cord Length (ft.) 10
Recommended Electrical Service 20A 120V
Input Phase Single-Phase
BATTERY
Full Load Runtime (min.) 4.5 min. (1920w)
Half Load Runtime (min.) 12 min. (960w)
Expandable Battery Runtime Extended runtime supported via optional external battery packs; 1600 watts maximum load with external battery packs
External Battery Pack Compatibility  BP48V24-2U (limit 1);  BP48V242UTAA (limit 1);  BP48V27-2US (multi-pack compatible);  BP48V60RT-3U (multi-pack compatible);  BP48V60RT3UTAA (multi-pack compatible)
DC System Voltage (VDC) 48
Battery Recharge Rate (Included Batteries) Less than 4.5 hours from 10% to 90%
Internal UPS Replacement Battery Cartridge  RBC94-2U 
Battery Access Front panel battery access door
Battery Replacement Description Hot-swappable, user replaceable batteries
Expandable Runtime Yes
VOLTAGE REGULATION
Voltage Regulation Description Automatic voltage regulation (AVR) maintains line power operation with an input voltage range of 83 to 145
Overvoltage Correction Voltage reduction of 12% applies when input is between 127 and 145
Undervoltage Correction Voltage boost of 12% applies when input voltage is between 96 and 108
Severe Undervoltage Correction Voltage boost of 24% applies when input voltage is between 83 and 95
USER INTERFACE, ALERTS & CONTROLS
Front Panel LCD Display Front panel LCD information and configuration screen offers detailed UPS and site power status and operating data, plus configuration of voltage, operating mode, alarm function and a variety of additional options (see manual for detailed LCD configuration and monitoring options)
Switches Power-fail alarm can be temporarily silenced using alarm-cancel switch; silent mode alarm configuration option available
Alarm Cancel Operation Power-fail alarm can be temporarily silenced using alarm-cancel switch; silent mode alarm configuration option available
Audible Alarm Audible alarm indicates UPS startup, power-failure, low-battery, overload, UPS fault and remote shutdown conditions
SURGE / NOISE SUPPRESSION
UPS AC Suppression Joule Rating 570
UPS AC Suppression Response Time Instantaneous
EMI / RFI AC Noise Suppression Yes
PHYSICAL
Installation Form Factors Supported with Included Accessories 4 post 19 inch rackmount
Installation Form Factors Supported with Optional Accessories 2 post rackmount (2POSTRMKITWM); Wallmount (2POSTRMKITWM); Tower (2-9USTAND)
Primary Form Factor Rackmount
UPS Power Module Dimensions (hwd, in.) 3.46 x 17.32 x 19.29
Rack Height (U Spaces) 2
Minimum Required Rack Depth (inches) 24.5
UPS Power Module Weight (lbs.) 57.6
UPS Power Module Weight (kg) 26.13
Shipping Dimensions (hwd / in.) 8.800 x 24.000 x 20.900
Shipping Weight (lbs.) 72.7000
Cooling Method Fan
UPS Housing Material Steel
Primary UPS Height (mm) 879
Primary UPS Width (mm) 4,399
Primary UPS Depth (mm) 4,900
ENVIRONMENTAL
Operating Temperature Range +32 to +104 degrees Fahrenheit / 0 to +40 degrees Celsius
Storage Temperature Range +5 to +122 degrees Fahrenheit / -15 to +50 degrees Celsius
Relative Humidity 0 to 95%, non-condensing
AC Mode BTU / Hr. (Full Load) 306
Battery Mode BTU / Hr. (Full Load) 1157
COMMUNICATIONS
Communications Interface USB (HID enabled); DB9 Serial; EPO (emergency power off); Slot for SNMP/Web interface
Network Management Cards SNMPWEBCARD; TLNETCARD;  WEBCARDLX 
Network Monitoring Port Description Supports detailed monitoring of UPS and site power conditions
PowerAlert Software For local monitoring via the UPS’s built-in communication ports, download PowerAlert Local software at http://www.tripplite.com/poweralert
Communications Cable USB and DB9 cabling included
WatchDog Compatibility Supports Watchdog application, OS and hard-reboot restart options for remote applications
Network UPS Tools Compatibility NUT compatible. See the full list of Tripp Lite NUT compatible UPS systems at http://www.networkupstools.org/stable-hcl.html?manufacturer=Tripp Lite
LINE / BATTERY TRANSFER
Transfer Time 5 milliseconds (line to battery mode); 1 millisecond (battery to line mode)
Low Voltage Transfer to Battery Power (Setpoint) 83
High Voltage Transfer to Battery Power (Setpoint) 145
SPECIAL FEATURES
Grounding Lug Back panel grounding lug
Cold Start (Startup in Battery Mode During a Power Failure) Cold-start operation supported
High Availability UPS Features Hot swappable batteries
Green Energy-Saving Features Greater than 95% efficiency - GREEN UPS; Individually controllable load banks
CERTIFICATIONS
UPS Certifications ENERGY STAR Qualified; Meets FCC Part 15 Category A (EMI); ROHS (Restriction of Hazardous Substances); TAA Compliant; Tested to CSA (Canada); Tested to NOM (Mexico); Tested to UL1778 (USA)
WARRANTY
Product Warranty Period (Worldwide) 2-year limited warranty
Connected Equipment Insurance (U.S., Canada & Puerto Rico) $250,000 Ultimate Lifetime Insurance